The HJ-DYZ-600 intelligent high-frequency switch-mode power system comprises a cabinet, AC distribution, rectifier modules (up to 12 fully configured), a monitoring module, and DC distribution. It offers comprehensive battery management-including low-voltage protection and optional load disconnect-plus temperature compensation, automatic voltage regulation, stepless current limiting, capacity calculation, online battery testing, and sleep energy-saving. Networked design with RS232/RS485 and dry-contact ports enables flexible networking, remote monitoring, and unattended operation, with full AC/DC surge protection and complete fault protection/alarm functions.
Invia Get Prezzo
| Parametri ambientali | Condizioni operative | Condizioni di trasporto | Condizioni di archiviazione | Standard applicabili | Commento | |||
| Categoria | Parametro | Unità | ||||||
| Condizioni climatiche | La temperatura | Bassa temperatura | ℃ | all'33 ottobre | all'40 ottobre | all'40 ottobre | Clausole 4.1.1 e 4.1.2 del regolamento YD/T 1058-2000. | Avvio a pieno carico a -40℃; declassamento lineare del 20% da +55 a +65℃. |
| Alta temperatura | ℃ | 65 | 70 | 70 | ||||
| Cambio di temperatura Temperature | ℃ / min | / | 1 | / | ETS 300 019-2-2 T2.3 | |||
| Temperatura ambiente di funzionamento | ℃ | -33-65 | temperatura di esercizio estrema a pieno carico | |||||
| Immagazzinamento | ℃ | -40-70 | ||||||
| Umidità | Umidità relativa | % | 5-90 | 90 (40±2℃) | / | YD/T 1058-2000 Clausola 4.1.3 | Short-term test: 0-95%, max 95%, non-condensing | |
| Condensazione | Si No | Nodo | Nodo | Si | ||||
| Pressione atmosferica | Bassa pressione | kPa | 86 | 70 | 70 | YD/T 1058-2000 Clausola 4.1.4 | Solo test del modulo | |
| Alta pressione | kPa | 106 | 106 | 106 | ||||
| altitudine | m | ≤ 4000 | Al di sopra dei 2000 m, ridurre la temperatura di 0.5 °C ogni 100 m aggiuntivi. | |||||
Nota: le specifiche sono soggette a modifiche senza preavviso per il miglioramento del prodotto. Scheda tecnica
Fully digital interleaved PFC innovative control with limited bipolar ZVS full-bridge topology, current-doubler rectifier topology, and dual MCUs for fully digital monitoring
Rectifiers use PFC so AC input current matches the voltage waveform and phase; high system efficiency saves energy and reduces OPEX
High-frequency PWM conversion reduces switching losses and EMI, allowing installation inside switching equipment rooms
Intelligent battery management with continuously settable equalization/float voltages and charge current limits via controller or remote system; supports float, equalization, and battery testing
Equipotential design across the cabinet improves EMC and lightning protection
È adatto a vari scenari di consumo energetico come edifici residenziali e edifici per uffici commerciali
Ci impegniamo a fornire un supporto rapido e professionale per garantire che le tue esigenze energetiche siano sempre soddisfatte con il massimo livello di servizio.
Siamo qui per rispondere alle tue domande e fornirti le soluzioni energetiche più adatte alle tue esigenze.